四虎最新影院 I 美女一区二区在线观看 I av不卡在线看 I 冲田杏梨 av作品在线 I 亚洲爆乳无码专区 I 特大色一区 I av综合av I 成人在线视频中文字幕 I 日韩精品免费在线视频 I 一级片黄色大片 I 99久久久无码国产精品试看 I 国内黄色小视频 I 91亚洲视频在线观看 I a久久久久久 I 午夜爽爽爽男女免费观看hd I 欧美 成人 亚洲 动漫 另类 I 四虎影院2019 I 肉耽高h男男1v1 I 成年片黄色日本大片网站视频 I 亚洲小说综合网 I 污的网站 I 波多野结衣中文字幕久久 I 又粗又猛又大爽又黄老大爷5 I 国产日产suv精品一区二区6 I 最新国产成人无码久久 I 欧美日韩一区二区精品 I 国产一区内射最近更新 I 巨粗进入警花哭喊求饶在线观看 I 污污网站观看 I 69国产精品成人 I 天堂а√中文最新版在线 I 2019精品视频 I 高贵麻麻被调教成玩物 I 精品国产精品网麻豆系列 I 韩国午夜小视频

網站公告-NOTICE

新聞資訊

當前位置:首頁 / 新聞資訊

濟南電纜橋架廠為你揭秘:橋架是鐵的,為何還要跨接地線?

  橋架就是專門用來托著和管理電纜、電線還有光纖的一個東西。在工廠啊、啊,還有各種建筑里面,都能看到它的身影,主要就是為了讓那些電纜的走線看起來整整齊齊的,看著舒服,而且還特別。說到這可能有人就想問了,橋架一般不都是鐵做的嘛,為啥還得弄個跨接地線呢?接下來就給大家好好說道說道。

  A cable tray is a device specifically designed to support and manage cables, wires, and optical fibers. It can be seen in factories, shopping malls, and various buildings, mainly to make the cable routing look neat, comfortable, and especially safe. When it comes to this, some people may want to ask, aren't cable trays usually made of iron? Why do we need to install a grounding wire? Next, I will explain it to everyone in detail.

  一、金屬橋架自身接地的局限性分析

  1、 Analysis of the Limitations of Grounding for Metal Bridge Structures

  1. 接觸電阻不可控

  1. Uncontrollable contact resistance

  橋架由多段拼接而成,連接處可能因油漆、氧化層、安裝間隙導致接觸不良,形成高電阻(即使肉眼看似緊密)。

  The bridge frame is composed of multiple sections spliced together, and the connection may have poor contact due to paint, oxide layer, and installation gaps, resulting in high resistance (even if it appears tight to the naked eye).

  例如:兩段橋架用螺栓固定,若接觸面有銹蝕,實際導電能力可能不足。

  For example, if two bridge sections are fixed with bolts and the contact surface is corroded, the actual conductivity may be insufficient.

  2. 動態風險

  2. Dynamic risk

  橋架長期使用后可能因震動、溫差變形導致連接松動,破壞原有的電氣通路。

  After long-term use, the bridge frame may become loose due to vibration and temperature difference deformation, which can damage the original electrical circuit.

  二、跨接地線的作用

  2、 The function of cross grounding wire

  1. 強制建立低阻抗通路

  1. Mandatory establishment of low impedance path

  通過銅編織帶或鍍鋅扁鋼跨接橋架各段,人為制造一條電阻≤0.1Ω的可靠路徑,確保漏電、靜電、雷擊電流能迅速導入接地網。

  By using copper braided tape or galvanized flat steel to bridge each section of the bridge, a reliable path with a resistance of ≤ 0.1 Ω is artificially created to ensure that leakage, static electricity, and lightning currents can be quickly introduced into the grounding grid.

  2. 防范“斷鏈”風險

  2. Prevent the risk of "chain breakage"

  即使某段橋架連接失效(如螺栓脫落),跨接地線仍能維持整體導電連續性,避免局部電位抬升引發觸電或電火花。

  Even if a certain section of the bridge connection fails (such as bolt detachment), the grounding wire can still maintain overall conductivity continuity, avoiding local potential rise and causing electric shock or sparks.

  三、針對不同材質的獨特處理方式

  3、 Unique processing methods for different materials

  四、遵循GB 50303標準的施工規范要求

  4、 Follow the construction specifications requirements of GB 50303 standard

  1.跨接位置

  1. Crossover position

  每段橋架連接處(含轉彎、分支處)必須跨接。

  Each section of the bridge connection (including bends and branches) must be bridged.base64_image

  長直線段每隔30m增設一次跨接。

  Add a crossover every 30 meters in the long straight section.

  2. 材料選擇

  2. Material selection

  優先使用銅質軟連接(截面積≥4mm?),耐彎曲且導電性。

  Priority should be given to using copper soft connections (cross-sectional area ≥ 4mm?), which are resistant to bending and have the best conductivity.

  若用鍍鋅扁鋼,截面積需≥25mm?,焊接后做防腐處理。

  If galvanized flat steel is used, the cross-sectional area should be ≥ 25mm ?, and anti-corrosion treatment should be carried out after welding.

  五、實際中應用

  5、 Practical application

  案例1:某工廠因未跨接地線,橋架連接處氧化導致接地電阻超標,設備外殼漏電時引發火災。

  Case 1: A factory caused a fire when the grounding resistance exceeded the standard due to oxidation at the bridge connection caused by the failure to cross the grounding wire, resulting in electrical leakage from the equipment casing.

  案例2:數據中心采用銅編織帶跨接,雷擊時橋架電位被強制拉平,保護了內部光纜免受電磁脈沖損壞。

  Case 2: The data center uses copper braided tape for bridging, which forcibly flattens the bridge potential during lightning strikes, protecting the internal optical cables from electromagnetic pulse damage.

  總結

  Summary

  跨接地線本質是“冗余設計”——用明確的低阻抗通路彌補金屬結構連接的不可靠性。這不僅是規范要求,更是對人身和設備的底線保障。下次看到橋架上的銅辮子,可以理解為電氣工程師在說:“別指望金屬自己導電,我親自給你焊條保命通道!

  The essence of cross grounding wire is "redundant safety design" - using clear low impedance paths to compensate for the unreliability of metal structure connections. This is not only a regulatory requirement, but also a bottom line guarantee for personal and equipment safety. The next time you see copper braids on the bridge, it can be understood as an electrical engineer saying, 'Don't expect the metal to conduct electricity on its own, I will personally provide you with welding rods to protect the passage!'!

  本文由 濟南電纜橋架 友情奉獻.更多有關的知識請點擊  http://www.zkhtkj.cn/  真誠的態度.為您提供為的服務.更多有關的知識我們將會陸續向大家奉獻.敬請期待.

  This article is a friendly contribution from Jinan Cable Bridge For more related knowledge, please click http://www.zkhtkj.cn/ Sincere attitude To provide you with comprehensive services We will gradually contribute more relevant knowledge to everyone Coming soon.

 