電纜橋架安裝常見質量缺陷問題
山東電纜橋架鋪設有多年的作業經驗,現在給大家說一下總結的關于電纜橋架安裝常見質量缺陷問題,希望大家在以后多加注意:
Shandong Cable Bridge Frame has been laid for many years. Now let's talk about the common quality defects of cable bridge erection summarized. I hope you will pay more attention in the future.
1.屬電纜橋架及其支架全長沒做牢靠接地(2處);
1. It belongs to the cable bridge and its bracket which are not grounded firmly (2 places);
2.電纜橋架與托架間未固定,橋架支架未做接地跨接線;
2. The cable bridge and bracket are not fixed, and the bridge bracket is not grounded.
3.越防火分區未做防火封堵;
3. No fire blockade was done in the more fire-proof zones.
4.合金橋架與鋼支架間未做防電化腐蝕的絕緣處置;
4. There is no insulation treatment to prevent electrochemical corrosion between alloy bridge and steel support.
5.支架未按防腐要求施工;
5. The bracket was not constructed according to the anticorrosion requirements.


6.地跨接線在橋架兩側隨意裝置或漏跨接,接地跨接線不設在顯眼側;
6. Ground spanning wiring is installed at random or leaky spanning on both sides of the bridge. Ground spanning wiring is not located at the conspicuous side.
7.頂內托盤、槽式橋架蓋板漏蓋;
7. Leakage cover of top tray and trough type bridge frame cover plate;
8.架銜接板的固定螺栓的螺母裝在橋架內側;
8. The nuts of the fixing bolts of the connecting plate are installed on the inside of the bridge frame.
以上內容均依據山東電纜橋架實踐工作中遇到的問題整理而成,供參考,如有問題請及時溝通、指正。我們的官網是:http://www.zkhtkj.cn謝謝合作。
The above contents are based on the problems encountered in the practice of cable bridge in Shandong Province. For reference, if there are any problems, please communicate and correct them in time. Our official website is http://www.zkhtkj.cn. Thank you for your cooperation.
上一篇:鋁合金電纜橋架的吊裝注意事項
下一篇:整套的電纜橋架的敷設安裝流程
下一篇:整套的電纜橋架的敷設安裝流程
相關文章 / Recommended news
- 濟南廠房福音!大跨距橋架破解3大痛點,加強筋加,安裝省一半錢
- 山東工程人警惕!橋架敷線踩這坑必返工,監理當場叫停,國標早有明確規定
- 濟南人避坑!橋架≠線槽,90%工程人都搞混,一字之差差千里
- 避坑指南!山東電纜橋架規格別瞎選,偏大浪費偏小隱患大,國標早就定好了
- 濟南人必看!鋁合金電纜橋架選對厚度,耐用又省心,90%的人選錯踩坑
- 山東人必看!電纜橋架不是“鐵架子”,藏著建筑用電的密碼,90%的人都不懂
- 800kg/m抗壓!濟南電纜橋架,破解3大工程痛點,工期省30%
- 3種類型+98%散熱!山東電纜橋架,選對不踩坑,布線效率翻倍
- 2類核心支架!濟南電纜橋架,抗震承重雙達標
- 別再混淆!山東電纜橋架vs線槽,6大核心區別一文分清
陽極氧化鋁合金橋架
托盤式電纜橋架
梯式電纜橋架
梯式不銹鋼電纜橋架
深灰色金屬防火電纜橋架